

Resistance, as per BS 6360
| Cross Sectional Area | Maximum Resistance at 20°C/Km | |||||
| Class - 1 Solid Copper Conductor |
Class - 2 Stranded Copper Conductor |
Class - 5 Flexible Copper Conductor |
||||
| Sqmm | Plain | Tinned | Plain | Tinned | Plain | Tinned |
| 0.50 | 36.0 | 36.7 | 36.0 | 36.7 | 39.0 | 40.1 |
| 0.75 | 24.5 | 24.8 | 24.5 | 24.8 | 26.0 | 26.7 |
| 1.00 | 18.1 | 18.2 | 18.1 | 18.2 | 19.5 | 20.0 |
| 1.50 | 12.1 | 12.2 | 12.1 | 12.2 | 13.3 | 13.7 |
Max. Mutual Capacitance
| Cross Sectional Area | Requirment as per BS:5308 Part - 1 | |||||
| Requirment as per BS:5308 Part - 1 | Cables with only collective screen (except 1 & 2 pair) | 1 Pair & 2 Pair with collective screen & all cables with individual pair screen | ||||
| Sqmm | (nF/Km) | (nF/Km) | (nF/Km) | |||
| 0.5 | 75 | 75 | 115 | |||
| 1.0 | 75 | 75 | 115 | |||
| 1.5 | 85 | 85 | 120 | |||
| L/R ratio (Max): | ||
| 1.5 Sqmm | - | 40 Micro Henry/Ω |
| 0.5/0.75/1.0 Sqmm | - | 25 Micro Henry/Ω |
| Operating Voltage : | 300/500V |
| Size : | Available in following no of pairs : 1, 2 (1 Quad), 5, 10, 15, 20, 30 and 50 Pairs |
| Conductor: | Solid/Stranded/Flexible Annealed Bare/Tinned copper class 1/2/5 to BS:6360 |
| Insulation & Pairing / Quading | Conductors are insulated with solid Polyethylene Type 03 as per BS:6234, uniformly twisted together to form a pair / quad with a max. lay length of 100 mm, and colour coded for identification. |
| Colour Code: | As per BS:5308 Part-1 |
| Pair shield(for individual pair Shielded cables only) | Each twisted pair shielded with aluminium backed polyester tape and a tinned copper drain wire of size 0.5mm² . |
| Assembly | Twister pairs are cabled with nonhygroscopic fillers if necessary |
| Overall shield | The entire assembly is shielded with aluminium polyester tape and a tinned copper drain wire of size 0.5mm². |
| Bedding:(applicable for Type 2 Cables) | Extruded Black Polyethylene Type 2 C or 03 as per BS:6234. |
| Wire Armouring (applicable for Type 2 Cables) | A serving of round galvanized steel wires as per BS:1442 is applied. |
| Sheath | Type - 1 & 2 Extruded Black PVC Type TM1 of BS:6746. |
Note:
1. Type 1 – Unarmoured,
2. Type 2 – Armoured
3. Other conductor Sizes and Types, Alternative Colour Codes, Higher Pair Count and Sheath Material – FR/FRLS/Zero Halogen compounds are available on request
4. As an alternate, armoured cables shall be supplied with Flat Strip/ Double Steel Tape/ Wire Braided as per customer requirement.