Aerial Bunched Cable
APPLICATIONS
Aerial Bunched Cables are
suitable for the following functions
mentioned as under:
In
theft prone areas.
As
replacement of bare lines in rural areas, in
woods, other localities & narrow street
where space is limited.
As
replacement of bare lines where reliability
of supply is of prime importance and where
high degree of stability of supply voltage
is of importance.
In hilly terrains where cost of
erection of overhead lines of under ground
cable becomes very high.
Where space
is limited like those in densely populated
area, dense forests.
As
reinforcement of existing system without
increasing voltage.
For
temporary supplies.
ADVANTAGES
Aerial Bunched Cables Lines have very high
reliability in maintaining services because
conductors are insulated with the best
dielectric. The benefits of using this line
are:
Safest
system because phase conductors are
insulated, no risk of danger of accidental
touching live conductor.
Less fault
rage on account of good protection against
line and ground fault by high winds or
falling trees or bird especially in hilly
areas & forests as encountered in rural
distribution networks.
High
insulation resistance to earth in all
seasons and polluted atmospheres. Negligible
leakage currents and low losses.
Multiple
circuits of power and telephone cables could
be strung in the same set of poles or any
other supports like walls etc.
Better
adaptability to “in concurrently with
existing over-head bare conductor system
without any interference.
High
capacitance and low inductance leading to
low impedance of lines.
Total lines
costs are reduced and maintenance is very
easy.
Insulation of conductors also helps
in preventing corrosion of the conductor.
Cores being
insulated, the chances of power thefts are
eliminated.
These are
cheaper than power cables.
Life of
Transformers increased as the supply
interruptions are minimized.
CABLE
CROSS SECTION
TECHNICAL PARTICULARS (AS per IS: 14255 - 1995)
Phase Conductor
(Aluminium)
As per IS 8130 : 1984
Street Lighting Conductor
(Aluminium)
As per IS 8130 : 1984
Messenger Conductor
Aluminium
Alloy
As per IS 398
(Part-4) : 1979
Nom. Area
Max. D.C. Conductor Resistance
at 20°C
Nom. Thickness of Insulation XLPE/PE
Nom. Area
Max. D.C. Conductor Resistance
at 20°C
Nom. Thickness of Insulation XLPE/PE
Nom. Area
Max. D.C. Conductor Resistance
at 20°C
Min. Breaking Load
Sqmm
Ohm/Km
mm
Sqmm
Ohm/Km
mm
Sqmm
Ohm/Km
KN
16
1.910
1.2
16
1.91
1.2
25
1.380
7.0
25
1.200
1.2
16
1.91
1.2
25
1.380
7.0
35
0.868
1.2
16
1.91
1.2
25
1.380
7.0
50
0.641
1.5
16
1.91
1.2
35
0.986
9.8
70
0.443
1.5
16
1.91
1.2
50
0.689
14.0
95
0.320
1.5
16
1.91
1.2
70
0.492
19.7
120
0.253
1.5
16
1.91
1.2
95
0.357
26.5
COMPOSITION & DESIGNATION OF L.T. AERIAL BUNCHED
CABLES
Designation
Complete
Bunched Cable
Approx. Overall Dia
Approx. Total Mass
mm
Kg/Km
3C x 16 mm2 + 25 mm2
+ 16 mm2
20
320
3C x 25 mm2 +
25 mm2 + 16 mm2
23
410
3C x 35 mm2 +
25 mm2 + 16 mm2
25
500
3C x 50 mm2 +
35 mm2 + 16 mm2
30
690
3C x 70 mm2 +
50 mm2 + 16 mm2
34
915
3C x 95 mm2 +
70 mm2 + 16 mm2
39
1195
3C x 120 mm2 + 70
mm2 + 16 mm2
44
1485
NOTES
We can manufacture Aerial Bunched
cable as per customer’s requirement meeting the
National/International specifications.